Discussed airflow with homeowner. Stated we could add dampers into basement to restrict flow for certain rooms and direct higher flow to the higher demanding rooms if adjusting registers doesn’t work out. Cooling preventative maintenance performed Check filter - 16x25x1 Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 40+5 @ 38.01+4.91 Check OD fan Amp - 0.75 Check compressor Amp - 6.12 Verify pressures and HP-SC/LP-SH Delta T - 20° The Air handler and AC are in optimal running conditions.