403 Headquarters Dr. Unit 5
Millersville, MD 21108
(443) 396-3797

Job Locations
for davidsonville, md


Map of Davidsonville MD
Michael W.

Michael W.


Job Checkin

Original call was to check power at front entry and laundry room near garage. Post lamp and driveway switch was tripping gfci in garage. I noticed the dimmer switch controlling a gfci, this application will never work. In addition there was a second receptacle on outside of garage being controlled as well. I recommended that the gfci be bypassed from the existing switch leg and to re feed the one outside garage to be bypassed from switch leg as well. Customer wished to us perform this solution. I bypassed the existing switchleg at gfci, disconnecting the exterior receptacle until we can return. Lastly, we installed the customer supplied switch at the front door and restored power to the front lights.we shall return next Thursday to complete scheduled work. We have returned and completed scheduled work. We have re-fed the existing exterior receptacle on garage from the interior GFCI. Lastly we have sealed around the existing junction box to prevent water from entering home. Exterior r