Reason for today’s call was GFCI circuit tripping. GFCI was connected to basement, outside receptacles, and garage. We saw that the culprit was a melted receptacle on the back deck. We also noticed in the panel there were multi wire branch circuits on single pole breakers, and no surge present. Customer opted to make all corrections. See below for work performed. Replace GFCI circuit with GFCI at each location Install two pole breakers for multi wire branch circuits Install Square D QO surge in main panel On a side note, we recommend installing a dedicated circuit for the outside heaters to keep them separate from standard branch circuit. Also, see attached for estimate to install light. Please call to schedule at your earliest convenience.