Service call for a 5-ton rooftop unit at a medical office. Found faulty TXV sticking closed and low suction pressure (~45 psi). Replaced TXV and recharged system with 9.3 lbs R-410A. Verified superheat at 12°F and subcooling at 9°F. Also replaced contactor and added surge protector for circuit protection. Unit now performing to spec.