PCSA 2022 Heating Check Up Prepaid. Gas furnaces is heating efficiently at this time, temperature rise is acceptable and filter is changed. Screw had come loose where flue pipe attaches to inducer motor leaving mild opening just enough for water to leak through, causing mild puddle in cabinet of system. Cleaned up water and re-tightened screw for flue pipe. Coupling for condensate line had also come loose causing water to drip from it. Re-attached and verified no water was leaking out of condensate line. Tested carbon monoxide detector and verified its operation. System checks out good at this time.