for merion station, pa


Map of Merion Station PA
Chris B.

Chris B.


Job Checkin

Service call that the Air Conditioner was not Cooling properly. Arrived onsite and spoke with Homeowner about issue. Found the Indoor Coil was completely frozen solid and the Drain Line was blocked due to the Coil being frozen causing the water to over Flow out of the Unit into the Auxilary Pan. Drained the Water and defrosted the Indoor Coil. On previous visit, we added Refrigerant to the system and Leak Dye. Used UV Light to examine the Indoor a Coil. Large amounts of Dye were present throughout the entire Indoor Coil, indicating that the Indoor Coil has a Refrigeramt Leak. Turned System back on and measured Refrigerant Charge. System was low on Refrigerant causing the Indoor Coil Temperature to be below the Freezing mark. Added 3lbs of 410-A Refrigerant to system, charging by Subcooling. We will follow up with options for Repair/Replacement of the Indoor Coil/AC System. Also recommend installing an EZ Trap and Wet Switch into the system. If the Wet Switch detects Water in the Au