Service call that the Air Conditioner was not Cooling the Home. Upon arrival, spoke with Homeowner about issue. Proceed to the Thermostat and turned System into AC Mode. Found the Blower was running but the Outdoor Unit was not turning on. Tested system and determined that the Outdoor Unit was out on Low Pressure due to being completely out of Refrigerant. Had added Refrigerant and Leak Dye to the System last year. Inspected Indoor Coil and found leak Dye throughout the Indoor Coil. Both the Indoor and Outdoor Units are from 2003. Due to age and condition, recommend replacement of the entire system. It is not recommended to replace just the Indoor Unit in this situation. Took measurements and photos of current system setup. Will follow up with an estimate for replacement. Turned the Disconnect at the Outdoor Unit Off. Left the Fan in the On position to help circulate air throughout the house.