System low on refrigerant again Pressurized with nitrogen Leaking on the Compressor discharge port Re-brazed joint Pressure tested for 30 minutes at 400psi 0.0psi drop Evacuated system Weighed in refrigerant charge Gave unit final charge via operating parameters vs charging chart in the product manual