System low on refrigerant again Pressurized with nitrogen Leaking on the Compressor discharge port Re-brazed joint Pressure tested for 30 minutes at 400psi 0.0psi drop Evacuated system Weighed in refrigerant charge Gave unit final charge via operating parameters vs charging chart in the product manual

System low on refrigerant again
Pressurized with nitrogen
Leaking on the Compressor discharge port
Re-brazed joint
Pressure tested for 30 minutes at 400psi
0.0psi drop
Evacuated system
Weighed in refrigerant charge
Gave unit final charge via operating parameters vs charging chart in the product manual System low on refrigerant again