Performed platinum heating maintenance Pulled blower housing and disassembled Cleaned blower wheel with water and brushes to remove drywall dust (Roughly 1 hour of labor) Pulled and cleaned flame sensor Pulled and cleaned burners with wire brush Pulled and flushed condensate trap Vacuumed out inside of furnace Vacuumed out wire connectors going into the blower cabinet (air gets pulled through those connectors and draws dirt into the connector pins) Run tested furnace in high and low fire Furnace is operating normally at this time, but did find signs of the inducer beginning to leak water.