April there 500 bypass humidifier leaking water through the cover onto the floor of the mechanical room in the garage Homeowners recently replaced the number 10 evaporator pad however the replacement media was installed sideways allowing straight flow through of the water at the same time the feet or tube was not fully inserted into the upper distributor reservoir allowing water to flow out of the plastic drain pan Clean plastic shroud, replace number 10 pad homeowner's already had on site and run test, adjust water pressure down for less waste in the drain