Performed cooling maintenance on geothermal packaged heat pump system: Filter good Air coil clean Blower wheel clean Put Condensate drain treatment tablets in the coil pan Primed the drain trap with water No condensate leaks found, drain flowing properly Compressor amps 21, rated 27 Capacitor 42mfd (under load), rated 40mfd Strapped reversing valve wiring off the bare copper TXV line to prevent a short circuit due to mechanical vibration Blower motor amps 2.2, rated 7.0 under full load No visual signs of internal water or refrigerant leaks No overheated wiring All electrical connections secure and tight Geo loop circulation pumps 1.8 amps, rated 2.14 total Domestic hot water generator functioning normally Zone dampers opening and closing properly System is in good working order at this time.