Replacement warranty. Upon arrival, furnace was locked out in code 13.1 for excessive limit trips. Reset furnace and test ran. Gas pressure was at 3.8inwc and on speed 8 fan which put the temperature rise above specs. Set gas pressure to 3.2inwc and set fan speed to 9. Test ran operation for approximately 20 minutes to verify operation.