Initial inspection found the 40 amp circuit breaker in the main panel in the basement in the tripped off or "never" turned on position in the middle. Testrianol equipment and heat pump mode heating and heat pump mode cooling. Refrigerant pressures are perfect in cooling mode and within specs in heating mode. Heat pump heating mode 101° f, heat pump cooling mode 47°f Inspect all control wiring inside and outside, confirm correct setup on furnace blower control board and Honeywell vision pro 8000 advanced setup 40 amp circuit pulling 13.7 at the breaker ***Electrical breaker appears warm to the touch and should be ambient temperature. Recommend electrician inspect or replace the heat pump breaker