Performed heating maintenance on an 8 year old Goodman 96% efficient single stage natural gas furnace 20x25x1 Filter is clean Pulled and cleaned the flame sensor Found signs of water leakage from the inducer motor Will be replacing inducer under parts warranty tomorrow Gas pressure 3.5"wc Temperature rise is 55⁰ Combustion test results were indicative of a healthy furnace and verify the heat exchanger is not compromised at this time Tested supply ductwork for carbon monoxide: measured 0ppm Inspector flagged exhaust pipe locations being too close to the AC condensing unit outside. **There is no code violation for this.** Moving the intake and exhaust pipes requires tearing out finished basement ceiling and making new penetrations through the exterior wall.