Performed heating maintenance on a Carrier 95% efficient single stage natural gas furnace 20x25x1 Filter is good, left the provided one next to the furnace Condensate trap is clear Blower capacitor measured 15.2mfd Pulled and cleaned flame sensor Run tested furnace Gas pressure set to 3.0"wc Temperature rise 53⁰ No water leaks present