Performed heating maintenance on a 2021 Trane two stage 80% efficient natural gas furnace 16x25x1 filter appears to be brand new No gas leaks detected Flue piping in good shape Blower in OK condition Pulled flame sensor and cleaned Cleared pressure switch port Burners in good shape Blower and inducer motors sound normal, amp draw in spec Run tested furnace High fire gas pressure set to 3.5"wc, temperature rise 37⁰ Low fire gas pressure set to 1.9"wc, temperature rise 35⁰ 0ppm carbon monoxide present around the furnace and water heater No concerns found on today's visit Furnace is operating within manufacturer's specifications at this time

Performed heating maintenance on a 2021 Trane two stage 80% efficient natural gas furnace 
16x25x1 filter appears to be brand new
No gas leaks detected
Flue piping in good shape
Blower in OK condition 
Pulled flame sensor and cleaned 
Cleared pressure switch port 
Burners in good shape 
Blower and inducer motors sound normal, amp draw in spec 
Run tested furnace 
High fire gas pressure set to 3.5"wc, temperature rise 37⁰
Low fire gas pressure set to 1.9"wc, temperature rise 35⁰
0ppm carbon monoxide present around the furnace and water heater
No concerns found on today's visit 
Furnace is operating within manufacturer's specifications at this time