Today’s visit was for annual safety assessment. We came across a few things of note that we addressed today. Please see below. Replace (3) breakers for multi wire branch circuits Install audible GFCI for sump pump Install GFCI for washer Bond water heater/ Ground cold water pipes Replace (2) broken receptacles on second floor We also saw that the receptacles and switches throughout the home are in pretty poor condition. They are backstabbed throughout the house and starting to fall apart. The connections on the back of the receptacle are becoming loose as well. We recommend doing a whole home re-device, or at least doing the second floor to start. Please see attached for solutions if you choose to move forward in the future.