-Arrived onsite and started in the garage to test the wire feeding the well system and everything on the panel end checked out and is verified working. I then was taken to the basement where i looked into the well pump switch, which also checked out fine and then the well control box. It was reading that there was a short on the load side. I unhooked the uf wire inside the pump box and tested between the 2 hot wires and there was a short reading between them, but nothing to the ground.I then went out to the yard and unbolted the top of the well and pulled the wire out that was connected to the uf wire and took apart the splice. I had no short going back to the house but the splices were also made up poorly. I tested the well wires that go down but got a normal reading at that moment. I did the splices properly and went inside to the well box and found that the well wires function in a normally open manner. So i did a regen test on the system to make it activate and circulate a lot of w