-arrived onsite and the resident showed us to the garage where the outlets where out, and then to the first bedroom where the power went out as well. Being as that the first bedroom is right on top of the garage, and the outlets are wire molded down into the garage from there, they are on together. We went to the panel and the breaker for that circuit was barely functioning at all, and the surrounding 2 arcfault breakers were extremely warm and had a weak throw as well. I recommended all 3 to prevent the other ones from going anytime soon and she wanted them all done, so we replaced all 3, power is restored and verified working.