i removed the gfci under the deck and the box due to the inside of the box being rusted because the screws to support the box was going through the back of the box. Also the wires coming to the top of the box were in romex connectors and are not allowed by code due to the fact water can get in through it. I re ran the wires so they all come to the bottom of the newly installed weather proof box i installed ( this box has supports on the outside of the box so water can get inside of box) then i installed a weather resistant gfci and a new in use bubble cover. I removed all double tapped neutrals in the panel and landed them on their own separate screws. This is done to prevent neutrals back feeding other circuits and also is accordance to the national electrical code #review