-Arrived onsite and gave an explanation of everything the whole home maintenance inspection and what was involved in that and then Tyler went upstairs and started by adjusting the attic fan because they didn’t feel it was running enough, but then adjusted it back to 105 degrees as a happy medium the residents picked. I started at the panel and found 2 shared neutral/ multifeed circuits, i found the bonding insufficient at the hot water heater and no gas bond, and the smoke detectors looked original to the house based off what i could see. I talked to him about a backup battery for his sump pump and a redevice while i was there as well, and also wrote up estimates for those to be done. Tyler replaced all 3 smoke detectors while i removed the 4 single pole breakers, and installed the 2, 2 pole breakers on the multifeeds, and installed the proper bonding as well. Once done, everything was tested and verified working.