1833 North Cameron Street
Harrisburg, PA 17103
(717) 236-9039

Job Locations
for hummelstown, pa


Map of Hummelstown PA
Service C.

Service C.


Job Checkin

Found Reach-In Cooler at 80 degrees. Compressor on roof was off. Tapped on the low pressure switch and compressor came on. Tapped again and it turned off. Replaced the low pressure switch. System is now running. Pressures are good. Had customer remove product from cooler so temp would come down faster. Temp control was set too high. Adjusted temp control for 38 degree temp. unit is down to temp.