Job Checkin

Homeowner stated that the unit is not cooling,, that it blows hot air, that they noticed the outdoor unit is not stopping,, that it seems to be running all the time. We started diagnostic at the condenser unit,,, we noticed the condenser fan motor wasn’t running, tested compressor/ condenser fan motor capacitor, tested OK,, tried to spin the motor but it was sealed, it moves slowly sometimes but stops right away,,,condenser fan motor née to be replaced,,( 1/4 hp,,,850 rpm ,,208-230 v). We have some concerns about the unit after motor replacement.. 1,, compressor was extremely hot to the touch, we don’t know how long it would last due to excessive stress and hot temperature was exposed. 2,, evaporator coil is extremely dirty causing lack of air flow this also adds more stress to the unit, is running longer periods of time to keep up with the temperature set at the thermostat. 3,,,duct work needs to be cleaned as well,,homeowner mentioned how important is for them to breathe good air qu