I arrived at Our clients home for a two system maintenance inspection. I began by testing and checking the electrical components on both outdoor condenser units. The upstairs condenser unit had multiple issues, including a failed capacitor, a burnt contactor and a blower motor that is overheating and pulling extremely high amps. The downstairs unit is running properly. I did rinse The condenser coils as part of today’s maintenance. I then proceeded outside and began to test the temperature drop on both systems. I found that the upstairs blower motor is also pulling high amps contributing to the wear and tear of the unit. The downstairs unit is cooling properly. I showed all my finances to our client and we discussed repairs versus replacement. He requested that I create and send options for a full system replacement for the upstairs the downstairs unit is cooling properly, but is working harder because the unit is struggling to maintain set temperature.