Upon arrival immediately met homeowner right outside front door. Homeowner explained to me that the last visit that he received was two months ago and they installed/modified his emergency/auxiliary drain pan and cleared out his primary drain line. Homeowner said that both indoor outdoor fans were running, but system still not cooling. Started diagnostics with indoor equipment. Did verify the drain pan had been replaced and also no water has retained. Checked: blower motor amps, capacitor(7.5mfd/still good), and cleanliness of blower motor wheel(dirty). Return plenum and single return air flex duct inner liner dirty. Ran diagnostics on outdoor condenser unit and found Extremely dirty condenser coils. 45/5Mfd dual run capacitor still good. Entry level hard start kit(supco). Compressor didn’t have continuity between windings. 2 1/2 Ton R22 system from 2011 While I was writing a paperwork, homeowner came out to service van and had fixify on phone. I turned on speakerphone and Verba