Client stated no heating for 5 ton package unit -A system has power, propane is present -Inducer motor is working properly, as well as pressure switch -However, the igniter is not receiving any voltage from the control board, resulting in the flame not being lit -The control board board needs to be replaced to get the heating elements back up to speed -Along with the igniter as it is in pretty rough condition