Reviewed home and concerns with Murali. Inspected duct system in attic and found many of the ducts were twisted and kinked which are reducing airflow. Recommend cutting ducts back and tightening up ducts. Also found insulation in 2/3 of the attic disturbed by work that was completed by construction. Recommend blowing in 12 inches of fiberglass in these areas. Inspected hot water and dehumidification system. Mechanical room is very hot. Recommend heat pump water heater to replace indirect water heater in basement so boiler can be shut down in the summer. Also recommend ducting dehumidifier to finished space in addition to crawl.