Arrived to get all information on systems and do heating maintenance on the boiler. System has 5 stats, 3 are two wire only and only control the heat, two are both heat and ac, there are two ac units upon the attic. Went over options about the stats and recommended Joe come out to go over all options between replacing equipment or just thermostats. As for the boiler, checked gas pressures, vacuumed out heat exchanger, checked combustion, checked leaving and returning water temps. System was working but the thermal limit was not always making contact and wouldn’t let the system run, replaced thermal limit and system is working correctly at this time.