520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Job Locations
for villanova, pa


Map of Villanova PA
Barry P.

Barry P.


Job Checkin

Found 3rd floor system 100KBTU two-stage Amana furnace not heating. Open high limit error code. Dirty filter. Encouraged homeowner to become a plan member for each system in the house. Homeowner decided to become plan member for this system alone for now. Replaced filter and performed heat tune up. Measured static pressure and temperature rise. Checked gas pressure. Checked ignitor. Cleaned flame sensor. Checked all controls, wiring, electric motors and components. Humidifier did not have a pad. Serviced humidifier and verified operation. Performed combustion test. Combustion/draft test: Passed We Have Serviced the other systems in the past. Furnace is operating well at the time of this service. Heat tune up under this new plan membership is comple.