View visual findings from this job here - https://visionshare.xoi.io/?id=XA-DE27-AC27A976FC064DC792B9D624FEC517A The daikin heat pump For the upper level is not working properly- The system is off at the thermostat when I arrived at the home- I proceeded to verify multiple things on the system * Replace the 14 x 25 by one air filter in the return grill * Both side sides of the evaporator coil are cleaner and clear with no obstructions * Confirm proper airflow through the return ductwork * Confirm proper airflow through supply ductwork * Confirm no obstructions in air handler or blower cabinet * Check outdoor condensing unit- no active faults * Connect gauges to outdoor condensing unit * Call for heating on the Honeywell thermostat * Heat pump system is on and running * Monitor refrigerant pressures and temperatures, Airflow and temperature splits- okay * Perform static pressure test on ductwork- ok * Monitor operations: after the system has been running for over 35 minutes notice h