View visual findings from this job here - https://visionshare.xoi.io/?id=XA-2F41-C9B73716A15F442C91C985D8C95A924C Customer has NO HEAT: * at arrival found Thermostat calling for heating * Check the steam boiler in the basement- System is off * Once again confirmed that the thermostat is calling for heating * Inspect the steam boiler * Found that the boiler was overfilled, and the cyclists was 100% filled up * The system is off on low water cut off for the McDonald and Miller with the Yellow flush valve * The float inside of the valve is stuck- After flushing the body and exercising the valve the boiler fires * I performed a steamed chemical treatment on the system of one month ago- There is no sign of any treatment inside of the boiler * Drain boiler down 100% * Then fill boiler and perform skimming of boiler, removing lots of mud and sediment from system * Drain boiler back down removing residual, dirty water and filled back up * After testing the boiler fires, but found that it w
Checked Goodman, gas fired furnace system was locking out due to air pressure switch not proving reset system and checked diagnose. The inducer for the furnace is faulty. due to abnormal sound coming from the inducer motor Highly recommend to replace the inducer and the air pressure switches. Office personnel please follow up with the landlord with a quote for the repairs please see photos for details please verify if this equipment is under extended warranty View visual findings from this job here - https://visionshare.xoi.io/?id=XA-2F41-3FCA0E3E70D744DB932B13AB84735AE0
Today I arrived on site Noise Investigation: Diagnosed the outdoor condenser unit as the source of the noise. Fault Identification: Confirmed the condenser compressor is making noise. Leak Detection: Discovered the Ductless HeatPump system is leaking, resulting in low pressure. Upon arriving at the property, the client explained that the outdoor unit has been making noise. I proceeded to verify the system. I found the system compressor making noise. I checked the system pressures. The pressures are low. I explained and showed the client the situation with the system. I recommended the client to consider replacing the entire system. This is a carrier ductless HeatPump s system with X3 indoor head. X1 condenser unit. The client understood the situation. I explained to the client that I would send all the information to management to be contacted on Monday to set up a visit with the project manager to discuss prices and options for new heating systems. Office to follow the clie
View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-3CC6AB79AF0847179DAD5B3C3E1DBB63 Customer is having issues with steam boiler and second floor radiator and bathroom is not heating up: The customer also stated at arrival that A plumber had looked at the boiler and stated that the system was overfilling. * At arrival confirmed the water level in the steam boiler is at a normal level- okay * Drain water from steam boiler testing low water cut off an automatic water feeder- Normal operation operations * Call for heating from Honeywell T6 Wi-Fi thermostat- Boiler fires * Test water cut off again to make sure that it is shutting down the main burner and confirm it filled water level back to correct level in sight class * boiler fires: Monitor system operations * Quickly found that the boiler is surging and pulling water down to a low water scenario where the boiler shuts down and the auto feeder kicks in- Water level gets too high overtime * The system is su
Completed heating maintenance on One steam boiler removed and clean burners and electronic ignition also clean burner trays removed pressure, trolls, and cleaned brass fittings reinstall turn system on checked lower cut off and automatic water fill check natural gas lines and also checked for carbon monoxide. None detected discussed with homeowner about replacement of thermostat which was declined. Left system working. View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-2EC87764436549B7BD7C90787580B581
View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-F328C5C619A743FE99F4C057FF5DD237 Return to replace expansion tank and relief of gas fire water boiler: At arrival, the boiler is on and running shut System down at service switch the current boiler pressure is just under 30psi and the relief valve is not dripping Isolated expansion tank at ball valve removed additional pressure from tank and removed the expansion tank from boiler piping the tank is completely filled with water - drain out bad tank and removed the from home installed and secured brand new expansion tank in boiler piping open ball valve to new expansion tank letting tank fill and monitoring boiler pressure- okay boiler pressure is back down at a normal 20psi return power to boiler and test system operations multiple radiant, radiator and hydro zones are calling and boiler fires- normal operations monitor boiler pressure and temperature- okay boiler then gets demand call for DHW- test and
Gas Hot Water Boiler. Perform a tune-up and cleaning to help ensure reliable and safe operation. Inspect for cracks & deterioration of Heat Exchanger. Check and clean Burners, brush and vacuumed-ok Check and clean thermocouple and pilot Assembly-ok Check Safety Controls-ok Check electrical wiring and components-ok Check GVD-Damper-N/A Check water feeder-ok Check back flow prevent-ok Check expansion tank-ok Check relive valve-ok Check Gas valve & Gas Line-ok Check Combustion Air, Flue pipe-ok Check Temperatures & Water pressure settings; Performance-ok Check and run Thermostats-okay Check circulation pump-okay Check zone valve operation-okay Water condition- ok Ran water heater, operating well at this moment. Run system, check radiators, all of them getting hot, left system operating well at this moment. No issues at this moment.. -/-/-/-/- - Richard Dominguez conducted an annual maintenance visit for the customer's boiler system. - The customer mentioned previous interactions with
View visual findings from this job here - https://visionshare.xoi.io/?id=XA-7C6F-33333D8316254752B0AF1CF18699BFB5 Customer is having an issue with the basement radiant heat zone as well as water leaking from the boiler: The customer brought me to the basement radiant heat thermostat at arrival to show me where he was having the problem He then brought me to the boiler room where water was on the floor I identified a leak at the system relief valve After testing, I found that with a call for heat or domestic hot water that the boiler pressure is rising above 30 psi and popping relief valve The expansion tank was found, filled with water and needs to be replaced as well as the relief valve on the system The basement radiant heat system was tested At first, the thermostat was set for Celsius Switch setting to Fahrenheit Test system operations- Call for heating from radiant floor thermostat- Zone valve opens and circulator pump is on and running Cycle uponor Thermostat on and off multipl
Today I arrived on site to address the gas valve issue. Service Actions: Replaced the gas valve on the heating system steam boiler. Ran and tested the system after the gas valve replacement. Current Status: System is operating correctly at this moment. Upon arriving at the property, the client gave me access to where the boiler unit is. I proceeded to verify the unit. Previously one of our diagnostic tech is defective gas valve. I proceeded to disassemble the defective gas valve. I proceeded to install the new gas valve. I proceeded to make the necessary connections and adjustments to conclude the repair. I tore the system. I did the gas leak test. No gas leaks present. I took the CO2 test. No CO2 present on this occasion. I concluded with the repair of the system. I showed the client the result of the installation of the new gas valve. The client thanked and was satisfied with the repair. This client was left with the system operating correctly at this time. View visua
View visual findings from this job here - https://visionshare.xoi.io/?id=XA-DE27-767EAEF2FBD64986BE5A8E87186C665D Checked Dunkirk steam boiler diagnosed the gas valve is compromised and highly recommend to replace the gas valve for safety and reliability concerns also recommend to perform a maintenance on the system and replace the igniter/flame sensor please see photos for more details Maintenance agreement for Dunkirk steam boiler
Upon arrival spoke with customer. Customer is explaining he’s hearing noise from air handler. Inspect air handler in the attic. Found that system is leaking air @ the seems @ hydro coil. 16 yr old Hydro unit it poor condition. Customer is speaking with Bryan about system replacement. Conducted recommissioning on interior of air handler. Seal all seams with aluminum tape to prevent air leakage. Clean return grill and replaced restricted filter. No more air leakage. Noise @ system is now when fan is running which is normal. System is back to normal operation. Recommending to customer to have duct cleaning and sanitizing done. Customer may follow up with the office when he’s ready to move forward. View visual findings from this job here - https://visionshare.xoi.io/?id=XA-DE27-79D303546B4342528B1360378BE6AA24
Completed heating maintenance on one steam boiler, removed and cleaned burners and igniter removed and clean pressure control and Brass fitting flushed, lower, cut off and tested turn system on checked operations, checked natural gas lines and check for carbon monoxide. None detected left system working
checked AO Smith, domestic hot water heater diagnosed water heater is leaking internally water heater Cannot be repaired and will have to be replaced. Please see photos and videos of water heater valves and access from street to existing water heater due to schools being in close proximity homeowner said Install technicians can park in her driveway to get equipment in location, shut water supply valves and discharge valve and also shut gas supply to water heater homeowner said that she has been having issues with her electricity and I recommend to her that we do electrical also can a office personnel please follow up with the homeowner
per maintenance on one steam boiler checked burners and standing pilot the system is unsafe to operate due to safety concerns as the relief valve is compromised and also the sight glass and it is not possible to remove the pressuretroll left system off as for safety concerns and issues Will have to replace the sight glass and repipe the pressuretroll (extended)reseal the chimney where the flue pipe goes in and replace the relief valve discussed the is plus the age of the system with homeowner and recommend a replacement of the boiler View visual findings from this job here - https://visionshare.xoi.io/?id=XA-213F-86614DA913514B62A9FF40F7B5125929
Upon arrival spoke with customer. Customer is explaining that he had a few people working on the boiler where parts were replaced. Customer was told parts that were replaced I.e Honeywell zone valve and relay should solve his problems. Customer is still having intermittent issues with the boiler where it will randomly fail to operate. Customer will reset boiler and system will begin to work once more. Customer reset boiler prior to arrival where system is operational, unable to diagnose a working system. Informed customer that based on the current condition of the boiler we could start a maintenance/recommissioning process to improve the condition of the boiler. At that time we can do a full assessment of boiler. Office to follow up with customer to schedule return visit for maintenance. View visual findings from this job here - https://visionshare.xoi.io/?id=XA-213F-92E097A7F4054D0BBC5062832D0A7DA7