Customer has no cooling in the entire house- She has a old York R22 condenser with coil Encased inside of custom ductwork on top of Armstrong furnace: At arrival, she stated the system stopped cooling over the weekend The thermostat is off at arrival with only the indoor fan on and running- Call for cooling Check the outdoor condensing unit Found only the outdoor condensing fan motor running, and the compressor off There is no capacitor for the compressor- This is a three phase contact with wires going directly from the contact to the compressor Check line voltage coming into the bottom of the contact- okay 204 v between each leg Check the line voltage coming out of the top of the contact- 118 and 70 volts Bad three phase contact this system is 24 years old and the furnace is 19 years old Gave customer the options to start with a contact replacement But it is possible that there are more issues Customer does not want to go down the diagnostic road and would like a quote for a full sys