View visual findings from this job here - https://visionshare.xoi.io/?id=XA-7C6F-2620ED034ED046F3AF3F51E0AA20B400 Customer has no heating on the second and And first floor of home: This zone is controlled by a zone Hydro air handler in the attic- Confirm at arrival that thermostats are calling for heat Check air handler in attic space: Found the system off: Found that the Hydro coil was extremely hot and hot water was circulating through the coil properly with a call for heat Found that the zoning panel was working properly and receiving the call for Heat and telling the system fan to turn on Confirm between G and common at the air handler 26 V- okay Indoor blower motor is not running The control board is making a loud buzzing sound at the relay Try tapping on the relay to get the motor to turn on but unsuccess As a temporary repair- Remove the black wire off of the blank terminal speed connection on the control board and connected it directly to 120 V- The blower motor is on and ru