View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A3D0-502FBC32A5864F8B86952AAFE7A91D63 Review and reconfigure newly installed T10 thermostats (3) for second and third floor AC system / review zoning : Customer stated that he is still having issues in the master bedroom zone and the daughter’s bedroom zone on the second floor after thermostat replacements. He Stated that only the third floor thermostat is turning on the air conditioning system At Arrival shut all thermostats off Called for cooling from the master bedroom thermostat- Noticed that only the fan is running and the compressor is not Called for cooling from the daughter’s bedroom thermostat- Found only the indoor blower running and compressor off as well Called for cooling on the third floor- Compressor is on and running Review system and wiring Found that the Y wire in the zoning panel was connected to O/B for the daughters bedroom- corrected wiring and relocate to Y terminal on zoning panel