Here to replace 1st floor evaporator coil, TXV and Transducer @ 1st floor condenser. Reclaim refrigerant at condenser. Remove condensate pump and drain line. Cut line set to remove evaporator coil. Brazed in stub copper piping @ New evaporator coil outdoor. Installed new evaporator coil, TXV and condensate drain pan. In existing cabinet. Reconnect drain line strap and secure. Remove condenser fan motor, remove electrical panel to access transducer. Unsweat transducer to install and braze in new transducer. Pressurized system with dry nitrogen. Check brazed joint and pro press joint with bubble solution for leak. No leak @ indoor or outdoor unit. Release dry gas and proceed to pull deep vacuum @ system. Once vacuum was pulled and held showing no signs of leak. Adjusted refrigerant charge by method of weighing-in. Standard factory charge is 11lbs-5oz after calculating line set length and doing the math that required to adjust refrigerant charge. Total charge is 12lbs-7oz. Took temperatur