View visual findings from this job here - https://visionshare.xoi.io/?id=XA-15F7-1DA2A48D780246C19E518F1EEDCF34C1 Customers condensate pump for the gas fire furnace / coil / condenser with bypass humidifier is tripping the GFI outlet: * At arrival, the furnace is on and running normally * The humidifier is also on and running to satisfy the humidity setpoint * There are no issues or false currently with the customers equipment * The customer states that the condensate pump occasionally tripped the GFI outlet and the customer has to reset it but when this happens, the furnace no longer operates * The condensate pump was tested with fresh hot water 6-7 times And operates 100% normally each and every time and does not trip GFI outlet - the EZ trap on the system was flushed and brushed clean and tested at this time as well * I spoke with the electrician with innovative air on site And determine the recommendation is to remove the GFI outlet and install a single 120 V Receptacle and i