View visual findings from this job here - https://visionshare.xoi.io/?id=XA-15F7-2BC4D30F89E54025A8D766EC2839910A Customer has no heating in the home: * At arrival, the boiler is showing an error code * Check the system limit string and found that the boiler is not closing on the low water cut off * This is an external low water cutoff on the system * Both mole connectors for the low water cutoff were checked and secured, and the low water cutoff was tried to be reset multiple times, but would not reset * Confirm with an external pressure gauge that the water pressure in the system is 20 psi and the water pressure is good * Remove the mole connector from the low water cut off on the control board inside of the boiler and install the factory Molex connector with a gray jumper wire * Return power to the boiler with a low water cut off bypass, and the system fires are properly * Immediately found combustion gas is leaking out from both the igniter and flame rod on the boiler as there