View visual findings from this job here - https://visionshare.xoi.io/?id=XA-57DC-D62A994A6F5840BEA2BBBC7DEF95BCBC Preform maintenance on x1 Carrier infinity gas fired furnace with bypass humidifier: * 6ft ladder needed to access system through x2 ceiling hatch’s * open furnace cabinet doors * shut power to system * removed flame sensor and hot surface igniter- cleaned sensor with copper bristle brush and polished clean with steel wool * inspected hot surface igniter- okay * brushed out and cleaned burner jet, furnace cabinet and components * inspected PVC fresh air and exhaust: okay * secured all electrical wiring and connections in furnace and blower cabinet * inspected blower motor/ wheel and assembly * removed condensate trap- flushed clean and primed with fresh water * removed neutralizer kit- has never been cleaned / replaced- customer approved * brought outside- dump minerals- washed and brushed clean- installed new minerals and put kit back together * reinstalled neutralizer