View visual findings from this job here - https://visionshare.xoi.io/?id=XA-57DC-12374C12E76F4E4FA4AD947C68022A47 Customer has no cooling on the first floor of their home from the space pack air with Lennox condensing unit: At Arrival the thermostat is off: * Call for cooling on the thermostat, but neither the indoor or outdoor unit are on and running * Check indoor air handler * System is showing an error for float switch * Reset error and system turns on * The drainage system on the first floor air handler is Completely backed up and full of sludge and debris * Spoke with customer over the phone as they are not home and got approval for repairs * Vacuum and brush primary pan 100% clean and clear * Vacuum vacuumed and brushed drain line and trap 100% clean and clear * Vacuumed and brushed condensate pump 100% clean and clear * Chemically treated primary pain and added condensate tablets * Tested all drainage- All water is flowing from inside primary pump through drain line into tr