View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-2E437C51873F49F2BAD36CB5C072620E Return to replace water feeder: * return to replace water feeder on gas water boiler * Over the weekend, Richard FaceTime the customer and they found that the boiler was low on water pressure reading 7.5 psi * The customer had to manually feed water into the boiler to get the pressure up to 15 psi and reset the system- No false or error since occurrence * This means that the water feeder was still closed and did not feed water into the boiler when the pressure drop below setpoint- Bad water feeder * Isolate water feeder from boiler * Removed existing water feeder from boiler * Pipe in and install brand new water feed/ Backflow Combi valve into supply water piping * Secure all the connections and confirm no leaks * Open valves so water feed is back in loop in the system- The water feeder slightly fills the boiler with more water-15.5 psi- okay * Confirm no leaks from the