View visual findings from this job here - https://visionshare.xoi.io/?id=XA-2F41-A6A81A2748064150851B288FD03F3003 Customer has no heating on the first floor in main entrance: * the nest thermostat is calling for heat at 70 degrees but indoor temp 63 * check the system in the basement and found that the zoning panel was not receiving the call for heat from the nest thermostat * when the nest thermostat was jumped out the zone panel responded and damper opens- ok * bad thermostat- customer approved replacement * shut power to system * removed nest thermostat * installed and wire in brand new T6 WiFi thermostat level and secure on wall in hallway * return power to system * configure thermostat and test system operations- with a call for heat zone 3 damper opens and is receiving call for heat and system on and running * test all other zones- operational * new thermostat is installed / tested / programmed to customers schedule and operational The thermostat is having trouble connecting t