Con-120 Upon arrival inspected 1st floor system. Found secondary overflow pan filled with water. Gave customer estimate to remove water. Customer agreed. Remove water and performed recommissioning on 1st floor system. Customer washable filter was restricted. Remove and replaced with standard 18x25x1 filter. Flush condensate drain line and clear EZ trap. Customer had blockage with drain line. Blockage lead to water overflowing into secondary drain pan. Condensate pump was tested to be operational. Pump discharge water 3-5times no issues. Check pressure and temperature to be stable. Low side 75psi / high side 275psi. Customer is aware of system using R-22 refrigerant type. Based on refrigerant type, system age and performance recommending that customer consider replacement options. System is back up and running and left operational @ this time. View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A3D0-958974C42F2C46A597E2840F3A1C0B9E