View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-B25148F406414264BE032CA843DEC4AA Preform maintenance on (2) Rheem gas fired furnaces with bypass humidifier- 6 ft ladder needed to access attic system: Replaced and dated (2) 12x12x1 and (2) 14x24x1 air filters in home Replaced Aprilaire # 45 humidifier water panel * Open furnace and blower cabinet doors * Removed flame sensors from systems * Removed spark igniter from systems * Cleaned both components with copper bristle brushes, and polished clean with steel wool * Reinstalled and secured components back into furnace * Vacuum and dusted out furnace cabinet and components, clean and clear * Vacuum and dusted out blower cabinet and components, clean and clear * blew out and vacuumed Electrical wiring, and components cleaner clear * Remove removed condensate traps from furnaces- flushed and washed clean and primed with fresh clean water and reinstalled * inspected neutralizer minerals in attic pump- wate