Refrigerant Customer is aware his system has a leak. System was charged with 1lbs 15oz of R-410A refrigerant. Customer is having the same issue with system loosing refrigerant charge. Customer agreed to adjust R-410A refrigerant. Customer is aware that a follow up is needed in 30-90 days to identify the source of leak. From dye testing that was conducted on 07/22/2025. Inspected system with UV light. Search was inconclusive more time is still required. Customer understand that there’s absolutely no warranty or refunds on lost/ leaked refrigerant. Customer assumes all risks of refrigerant costs until a leak has been identified and repaired fully. It was also explained that there’s no guarantee on how long refrigerant that was added may last. Refrigerant charge was adjusted to normal operation. Low side 135psi / High side 375psi Earlier pressures were found where low side pressure was 95psi / high side 305psi Check temperature split before adjusting refrigerant charge supply 71.7 F deg