View visual findings from this job here - https://visionshare.xoi.io/?id=XA-D939-13E696FA4B0847BD8BEF62640AF203CD Customer has no cooling from master bedroom AC system: - Maytag R22 system At arrival found indoor thermostat calling for cooling but neither the indoor or outdoor system are on and running * check air handler in attic * Found the system off on internal condensate pump safety switch with little water in the overflow pan for the pump * The pump is making a humming noise and trying to run, but it is burnt out * The pump is hot To the touch as well as the water inside of it from drawing high amps * Explain findings to customer and recommended condensate pump replacement- Customer approved * Removed existing condensate pump and internal safety from system * Disconnected discharge line from existing condensate pump * Removed all water in pump pan * Installed and set new 220 V condensate pump in place inside of pump pan * Connect and secure discharge line to new condensate pum