View visual findings from this job here - https://visionshare.xoi.io/?id=XA-57DC-FDF76AD9692A4CF18B1DED3DF8008A56 Customer has no cooling on the first floor of their home from the Unico high velocity air handler with Daikin condensing unit: * At arrival thermostat is calling for cooling * The indoor blower motor is on and running * The outdoor condensing unit is off * Check the outdoor condensing unit * Found that there was no 24 V getting sent to the contact * Found that there was no LED lights lit on the core diagnostic board * Disconnected indoor wire from condensing unit and checked voltage- Was bouncing between 0.00-9 volts * Check the condenser wire from the unit going into the house- No visible brakes * Check power again at Low-voltage condenser wire- The wire now has 24 V to it * Connect condenser wire back to low voltage connection- Contact pull in and condensing unit is on and running * Check and monitor refrigerant pressures and temperatures at condensing unit- ok * Check