Performed cooling maintenance on a 2011 Carrier Infinity 2 stage AC system Filter is good Closed humidifier bypass damper to summer position Drain is clear No signs of water leakage from the furnace that may have developed during heating season Connected wireless probes to the system See attachment for readings Everything refrigerant and airflow related is within manufacturer's specifications Capacitor tested 42mfd during operation Tore down and washed Condenser coil from the inside out System is in great shape for its age