Cooling preventative maintenance performed Check filter - 20x25x1 clean Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 50+5 @ 48.81+4.99 Check OD fan Amp - 0.63 Check compressor Amp - 6.82 Verify pressures and HP-SC/LP-SH Delta T - 19° The Air handler and AC are in optimal running conditions.