Cooling preventative maintenance performed Check filter - 20x25x1 clean 5/25 Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD -50+5 @ 50.3+4.96 Check OD fan Amp - 0.65 Check compressor Amp - 7.02 Verify pressures and HP-SC/LP-SH 257-3°/118-7° Delta T - 21° The Air handler and AC are in optimal running conditions.