No cool caused by overheated and shorted open compressor terminal on the dual run capacitor 440 volt power supply. Compressor reading 0 MFD fan motor 4.8 Install replacement 440 volt power supply 45 + 5 Perform 2025 ESA PMI cooling season while on site. Contactor is in very good condition, clean electrical compartment and test fan motor and compressor operation, water flush condenser coil and run test refrigerant pressures. 16x25x4 plated air filter is on schedule with homeowner. Minor modifications to the cabinet to aid in the ease of replacement of the filter media, visual inspection of the evaporator in coil all aluminum downflow system, noticed minor water staining from water blow off but does not appear to be affecting anything or wet at this time. Water flush coil drain pan and drain lines to the floor drain of the second floor mechanical room Bryant programmable thermostat is functioning correctly in cooling mode and does not carry batteries. System is clean safe and ready fo